4–20mA Pressure Transmitter: How It Works, Wiring, Scaling and Testing

In the field of industrial process control, 4–20 mA pressure transmitters serve as core sensing devices. The 4-20mA pressure transducer converts the pressure in the process into a loop current. The 4-20mA signal has a linear relationship with the pressure range. Thanks to their excellent noise immunity and stable transmission performance, 4–20 mA pressure transmitters are widely used for the precise acquisition and long-distance transmission of pressure data, making them essential components for ensuring the safe and efficient operation of industrial systems.

Definition of 4-20mA pressure transmitter

A 4–20 mA pressure transmitter is a pressure sensor with its own electronics. The sensing element (diffused silicon, ceramic or capacitive) puts out a weak signal; the electronics amplify it, correct it for temperature and turn it into a DC current. 4 mA stands for the lower range value and 20 mA for the upper range value, so a 0–10 bar unit sends 12 mA at 5 bar. Most units are two-wire: one pair of wires carries both the 24 VDC supply and the signal.

High Accuracy oil and gas pressure sensor

Principle of 4- 20mA pressure transmitter

Pressure sensors work by sensing pressure and converting it into electrical energy. Piezoresistive, capacitive, and diffused silicon are the most common types used in industrial applications.

The resistance of a piezoresistive material, measured in ohms (Ω), changes when it is stretched or compressed. Piezoresistive pressure sensors consist of a micromachined silicon diaphragm with piezoresistive strain gauges diffused into it. The diaphragm is fused to a silicon or glass backplane. The sensor contains resistors, usually arranged in a Wheatstone bridge circuit. As pressure increases on the piezoresistive material, it offers a greater resistance to the flow of current. This results in an output from the Wheatstone bridge, measured in millivolts, that is proportional to the pressure.

Capacitive pressure sensors use a thin film as one plate of a capacitor. The diaphragm is typically a metal or metal-coated quartz element. One side of the diaphragm is subjected to a reference pressure, and the other side is subjected to the process pressure. Changes in pressure cause slight deformations of the pressure sensing plate, which in turn cause changes in capacitance. These changes in capacitance are proportional to the pressure applied to the plate that is exposed to the process.

In a diffused silicon pressure transmitter, process pressure acts on a 316L isolating diaphragm. Silicone fill oil passes it to a silicon chip with strain gauges diffused into the surface. The gauges change resistance, and the electronics turn that change into a 4-20mA signal proportional to pressure.

High-temperature 4-20mA pressure transducers with cooling fins

Advantages of 4–20 mA Pressure Transmitters

High immunity to interference: Current signals are largely unaffected by electromagnetic and radio frequency interference, so they remain stable even near variable frequency drives and high-power motors—exactly the kind of harsh industrial environments where other signal types would struggle.

Long transmission distance: Cable resistance does not change a current signal, so run length is limited by the supply voltage, not by accuracy. With 24 V, runs of several hundred metres are routine and no signal booster is needed.

Automatic open-circuit detection: The 4 mA “live zero” means any reading below that threshold points straight to a broken wire or sensor failure, so technicians can pinpoint problems quickly. The 0–20 mA range simply can’t tell the difference between a genuine zero reading and a disconnected circuit.

Two-wire power supply simplifies wiring: Using loop power means one cable pair carries both the signal and the operating power, which cuts down on both cable runs and installation headaches.

Intrinsically Safe Explosion Protection: The loop runs at low voltage and low current, which makes intrinsically safe designs practical. In a hazardous area you still need an Ex ia transmitter and a safety barrier or isolator.

Excellent Standard Compatibility: Since 4–20 mA is the de facto standard across industrial automation, it plugs directly into PLCs, DCSs, data acquisition cards and most other control hardware without compatibility concerns, and replacement parts are easy to source.

Support for superimposed digital communication: The HART protocol, based on 4–20 mA, allows digital information to be superimposed onto the analogue signal, enabling remote parameter configuration and equipment diagnostics, thereby meeting the needs of both traditional systems and intelligent upgrades.

Wiring of a 4- 20mA pressure transmitter

Most of our pressure transmitters have a two-wire 4-20mA output. The transmitter, the 24 VDC supply and the PLC analog input are wired in series in a single loop. The first diagram below shows a sensor with a DIN 43650 plug, the second a transmitter with a terminal box. For three-wire and four-wire versions, see the linked wiring guide.

4-20mA pressure transducer two-wire wiring diagram (DIN 43650 connector)
Two-wire 4-20mA loop wiring on a pressure transmitter terminal block

How to Scale a 4–20mA Signal to Pressure

The loop current follows the transmitter’s calibrated range in a straight line. To turn a reading back into pressure:

P = LRV + (I − 4 mA) × (URV − LRV) / (20 mA − 4 mA)

  • LRV / URV – the lower and upper range values on the nameplate or calibration certificate, e.g. 0–100 kPa or −10 to 50 kPa.
  • I – the measured loop current, normally between 4 and 20 mA.

Example: 0–100 kPa transmitter

  • 12 mA: P = 0 + (12 − 4) × (100 − 0) / 16 = 50 kPa
  • 8 mA: P = 0 + (8 − 4) × 100 / 16 = 25 kPa

Example: −10 to 50 kPa (negative lower range value)

  • 16 mA: P = −10 + (16 − 4) × (50 − (−10)) / 16 = −10 + 45 = 35 kPa

The other way round: which current should a given pressure produce?

I = 4 mA + (P − LRV) × 16 mA / (URV − LRV)

On a 0–100 kPa unit, 75 kPa should read 4 + 75 × 16 / 100 = 16 mA. Work this out before you check a transmitter with a hand pump, so you know what the meter ought to show at each test point.

The signal itself carries no unit. A customer running a hot-air system at a paper plant in France asked us exactly that about an SI-2088 we had calibrated to ±5000 Pa gauge. Our answer: 4 mA is −5000 Pa, 12 mA is zero, 20 mA is +5000 Pa, and the PLC must be scaled to the range printed on the calibration certificate. Scale it to 0–5000 Pa by mistake and every reading is off, even though the transmitter is working.

Need a voltage input instead? A 250 Ω precision resistor (0.1% or better) across the input turns 4–20 mA into 1–5 V; 500 Ω gives 2–10 V. Neither one is 0–10 V. For a true 0–10 V signal, use a signal converter, and make sure the supply voltage still covers the extra drop across the resistor.

How to Test a 4–20mA Pressure Transducer

Step 1: Check the installation

Most of the pressure transmitter failures are caused by improper use and installation of pressure sensors, which can be summarized in several aspects.

  1. The primary element (orifice plate, remote measurement joint, etc) is blocked or the installation form is incorrect and the pressure point is unreasonable.
  2. The pressure pipe leaks or is blocked, there is residual gas in the filling pipe or residual liquid in the filling pipe, and there are sediments in the transmitter process Flange, forming a measurement dead zone.
  3. The transmitter wiring is incorrect, the power supply voltage is too high or too low, and the connection between the indicator head and the instrument terminal is poor.
  4. The installation is not strictly following the technical requirements, and the installation method and site environment do not meet the technical requirements.

Step 2: Appearance inspection

Check whether the appearance of the sensor is obviously damaged, cracked, or deformed. If damage is found, it may affect the performance and accuracy of the sensor.

1. Check the sensor housing

Check whether the housing of the sensor is cracked, deformed or damaged. The integrity of the housing is very important for protecting the internal components of the sensor.

2. Check the cable connection

Check whether the cable connection of the sensor is stable, loose or broken. A poor cable connection may cause unstable or distorted signal transmission.

3. Check the interface

Check whether the interface of the sensor is clean and whether there is dirt or foreign matter. The cleanliness of the interface is very important to ensure the accuracy of signal transmission.

Step 3: Electrical characteristics test

 By testing the output signal, input resistance and other parameters of the sensor, the performance and accuracy of the sensor can be judged.

1. Test the output signal

Connect the sensor to the test instrument, set the corresponding pressure value, and observe whether the output signal of the sensor is within the range of 4- 20mA. If the output signal is out of range, it means that there may be a problem with the sensor.

2. Test linearity

Test the output signal of the sensor at different pressures and observe whether the relationship between the output signal and the pressure value is linear. If the linearity is not good, it means that there may be a problem with the accuracy of the sensor.

Step 4: Temperature characteristic test

By testing the performance of the sensor at different temperatures, the stability and reliability of the sensor can be determined.

1. Test temperature drift

Place the sensor in different temperature environments and observe whether the output signal of the sensor changes. If the temperature drift is large, it means that there may be problems with the stability of the sensor.

2. Test temperature compensation

For sensors with a temperature compensation function, test whether their output signals are consistent at different temperatures. If the temperature compensation effect is not good, it means that there may be problems with the reliability of the sensor.

Step 5: Pressure characteristic test

By testing the output signal of the sensor at different pressures, the accuracy and stability of the sensor can be determined.

1. Test the zero point

Place the sensor in a zero pressure environment and observe whether the output signal of the sensor is 4mA. If the zero point deviation is large, it means that there may be problems with the accuracy of the sensor.

2. Test range

Place the sensor in the maximum pressure and minimum pressure environments and observe whether the output signals of the sensor are 20mA and 4mA, respectively. If the range deviation is large, it means that there may be problems with the stability of the sensor.

3. Test repeatability

Under the same pressure environment, measure the output signal of the sensor multiple times and observe its fluctuation range. If the repeatability is poor, it means that there may be problems with the stability of the sensor.

Step 6: Environmental adaptability test

By testing the performance of the sensor in different environments, the adaptability and reliability of the sensor can be judged.

1. Test anti-interference ability

In environments with electromagnetic interference, vibration, etc. test whether the output signal of the sensor is stable. If the anti-interference ability is poor, it means that there may be problems with the reliability of the sensor.

2. Test pressure resistance

In a higher-pressure environment, test whether the output signal of the sensor is stable. If the pressure resistance is poor, it means that there may be problems with the adaptability of the sensor.

3. Test temperature resistance

In high or low temperature environments, test whether the output signal of the sensor is stable. If the temperature resistance is poor, it means that there may be problems with the adaptability of the sensor.

Featured products

Industrial Diffused Silicon Pressure Transmitter
General Purpose Industrial Pressure Transmitter
SI-3151 Capacitive Pressure Transmitter
SI-3151 Capacitive Pressure Transmitter
SI-2088 Customizable High Temperature Pressure Transmitter
SI-2088 Customizable High-Temperature Pressure Transmitter
Flameproof Pressure Transmitter Exd Explosion proof
Flameproof Pressure Transmitter Exd

Troubleshooting of 4- 20mA pressure transmitter

No current output from the pressure transmitter

  1. Check whether the power supply of the pressure transmitter is connected in reverse; connect the power supply polarity correctly.
  2. Measure whether the power supply of the pressure transmitter has a 24V DC voltage; generally, the power supply voltage of the transmitter must be greater than 12V. If there is no power supply, check whether the circuit is disconnected and whether the instrument is selected incorrectly. For example, the input impedance should be less than 250 ohms.
  3. If it is with a meter head, check whether the meter head is damaged (you can short-circuit the two wires of the meter head first. If it is normal after short-circuiting, it means that the meter head is damaged); if the meter head is damaged, replace it.
  4. Connect the ammeter in series to the 24V power supply circuit and check whether the current is normal;  if it is normal, the transmitter is normal, and other instruments in the circuit should be checked at this time.
  5. Check whether the power supply is connected to the power input terminal of the transmitter.

The output current of the pressure transmitter is greater than 20mA

  1. Is the range set correctly? Some smart transmitters output 21 mA or more as a high alarm (NAMUR NE 43). Check the alarm setting.
  2. Does the actual pressure exceed the selected range of the pressure transmitter? In this case, a pressure transmitter with an appropriate range should be selected again.
  3. Check whether the pressure sensor is damaged. Severe overload sometimes damages the isolation diaphragm.
  4. Is the power cord connected correctly? The power cord should be connected to the corresponding terminal.

The output of the pressure transmitter is less than 4mA

  1. Is the power supply of the transmitter normal? If it is less than 12 volts, check whether there is a large load in the loop, and the input impedance of the transmitter load should meet the requirement that RL is less than the transmitter power supply voltage -12V/20mA ohms.
  2. Is the pressure below the lower range value, for example vacuum on a gauge unit? Many transmitters then drop below 4 mA. A reading of 3.6 mA or less can also be a low alarm.

The digital pressure transmitter does not display correctly

  1. Is the transmitter power supply normal? If it is less than 12V, check whether there is a large load in the circuit. The input impedance of the transmitter load should meet the requirement that RL is less than (transmitter power supply voltage – 12V)/20mA ohms.
  2. Is the reference pressure value correct? If the reference pressure gauge has low accuracy, replace it with a pressure gauge with higher accuracy.
  3. Is the range of the pressure indicator consistent with the range of the pressure transmitter? The range of the pressure indicator must be consistent with the range of the pressure transmitter.
  4. Is the input of the pressure indicator correct with the corresponding wiring? If the input of the pressure indicator is 4- 20mA, the transmitter output signal can be directly connected. If the input of the pressure indicator is 1- 5V,a resistor with an accuracy of one thousandth or more and a resistance of 250 ohms must be connected to the input end of the pressure indicator, and then connected to the input of the transmitter.
  5. The input impedance of the transmitter load should meet the requirement that RL is less than (transmitter power supply voltage -12V)/20mA ohms; if it does not meet the requirement, corresponding measures can be taken according to the different requirements, such as increasing the power supply voltage (but must be lower than 36V), reducing the load, etc.
  6. Whether the corresponding equipment housing is wired, the equipment housing is grounded.
  7. Whether the wiring is separated from the AC power supply and other power supplies; the wiring is separated from the AC power supply and other power supplies.
  8. Whether the pressure sensor is damaged. Severe overload sometimes damages the isolation diaphragm; it needs to be sent back to the manufacturer for repair.
  9. Whether there are sand, impurities, etc. blocking the pipeline in the pipeline. If there are impurities, the measurement accuracy will be affected; impurities need to be cleaned and a filter should be added in front of the pressure interface.
  10. Whether the temperature of the pipeline is too high. The operating temperature of the pressure sensor is -25~85℃, but it is best to be within -20~70℃ in actual use. Add a buffer tube to dissipate heat. It is best to add some cold water to the buffer tube before use to prevent superheated steam from directly impacting the sensor, thereby damaging the sensor or reducing its use.

FAQ

How far can you run a 4–20 mA signal?

Theoretically, a 4–20 mA signal can be transmitted over a distance of several kilometers. In practical applications, however, the range typically spans from several hundred meters to a few kilometers, depending on factors such as wire resistance, supply voltage, and load resistance.

Theoretically, using a wire with a nominal cross-sectional area of 1.5 mm², a 4–20 mA signal can be transmitted up to 2,626 meters. With a nominal cross-sectional area of 0.8 mm², the maximum transmission distance is 1,400 meters.

In real-world scenarios, the actual allowable wire length is usually slightly shorter than the calculated value, as the nominal cross-sectional area specified for wires is often slightly higher than the actual value.

Why does the signal start at 4 mA, not 0?

It’s quite simple: if 0 were the minimum value, it would be impossible to detect an open-circuit fault!

During normal operation, the current signal will not fall below 4 mA. If the transmission line breaks due to a fault, the loop current drops to 0. A value of 2 mA is commonly used as the threshold for an “open-wire” alarm.

There are two reasons for this. First, it helps avoid interference. Second, 4–20 mA systems typically use a two-wire configuration, where the same two wires serve as both the signal path and the power supply; the 4 mA baseline provides the necessary quiescent (static) operating current for the sensor’s circuitry.

How do I check the mA output with a multimeter?

The most accurate method is to disconnect one wire and insert the multimeter into the loop—this approach works for any device. Alternatively, measurements can be taken without disconnecting any wires by probing the analog input terminals of a PLC or DCS, or the 4–20 mA output terminals of the device itself. Prerequisites:

  1. The loop impedance must be significantly higher than the internal resistance of the multimeter. Consequently, while some devices allow for accurate mA-range current measurements without disconnecting any wires, others cannot be measured this way—or will yield highly inaccurate readings.
  2. This measurement method is only applicable to 3-wire or 4-wire devices. In 2-wire systems, the signal and power share the same loop; attempting to measure current without disconnecting wires can either blow the multimeter’s fuse or result in an abnormally high mA reading. (For example, in Honeywell’s PKS system, if a multimeter set to the current range is connected to a 2-wire input loop, the I/O module will limit the current to approximately 90 mA—preventing the fuse from blowing, but producing an erroneous, out-of-range reading.)

Through the article, you can solve some fault problems by yourself. If you need more knowledge about a 4- 20mA pressure sensor, please contact us. If you need to buy a pressure sensor. Please contact us! We will provide you with professional answers and services. Sino-Inst is experienced, has a reasonable price and can support OEM. Come and contact us!!!

Welcome To Share This Page:
Product Categories
Latest News
Get A Free Quote Now !
Contact Form Demo (#3)

Related Products

Related News

As key perception components in industrial measurement and control systems, pressure sensors are widely used in various working conditions. Types

Hydrostatic pressure transmitters operate on the principle of hydrostatics. This implies that they are capable of detecting the pressure generated

As a core component that bridges the gap between physical pressure signals and processable electrical signals, the pressure transducer relies

Pressure Transmitter Installation can greatly affect the accuracy of pressure measurements. Pressure transmitter is an instrument used to measure the

Absolute Pressure Sensor or absolute pressure transmitter is what we often hear when choosing industrial pressure transmitters. So what is

Three-wire pressure sensors are a pretty common type of sensor. They connect to the controller via three wires and are

A pressure transducer is a critical instrument used in various industrial process applications. And their measurement accuracy usually impacts industrial

A pressure transducer is equipment that measures pressure. It is commonly used in industrial automation control systems. By converting pressure