Orifice Flow Meter Installation: A Complete Step-by-Step Guide

Orifice flow meters measure flow based on the principle of differential pressure caused by throttling, and the measurement results are highly sensitive to the state of the flow field. Correct installation is key to eliminating flow field distortions and ensuring measurement accuracy; this article outlines the key installation points in accordance with relevant standards.

What is an Orifice Plate Flow Meter?

The orifice plate flow meter is a differential pressure flow measurement instrument. It is a common throttling flow meter and is widely used. It consists mainly of a standard orifice plate, pressure tapping devices and a differential pressure transmitter.

It is a common measurement of the volume or mass flow rate of gasses, liquids and steam in pipelines. It is simple in structure, low in cost and high in reliability and widely used in chemical, power generation, oil and gas, water treatment and other industries.

Working Principle of Orifice Plate Flow Meter

The working principle of orifice plate flow meter is based on throttling. If a fluid flows with a constant velocity through a pipeline and passes through an orifice plate installed at the center of the pipeline, the flow cross-section is suddenly narrowed. This causes the fluid velocity to increase and the static pressure to drop correspondingly, creating a stable pressure differential across the orifice plate.

The greater the fluid flow rate, the greater the differential pressure generated upstream and downstream of the orifice plate. A differential pressure transmitter measures this pressure difference; by combining this with the fluid medium parameters and the dimensions of the pipeline and orifice plate, and applying a flow calculation formula, the real-time flow rate of the fluid within the pipeline can be determined.

Main Components of an Orifice Plate Flow Meter

Throttling element (orifice plate insert): The core component, consisting of a thin plate with a precisely centred aperture. As the fluid flows through this point, the cross-sectional area contracts, generating a differential pressure between the upstream and downstream sides. Types include standard orifice plates, eccentric orifice plates and segmented orifice plates.

Pressure-taking assembly: It includes pressure-taking orifices, annular chambers, pressure-taking flanges and pressure-conducting tubes. This is used to take pressure signals from upstream and downstream of the orifice plate. Common pressure tapping configurations are the angle-mounted, flanged and radial pressure tapping.

Straight pipe sections measurement: The upstream and downstream measuring pipes ensure a stable flow field entering the orifice plate and minimize the effect of vortex disturbances on the accuracy of measurement.

Sealing and fastening components: The orifice plate is clamped and secured by means of flanges, bolts and nuts and sealing gaskets, preventing leakages of medium.

Differential pressure signal components: Differential pressure transmitters and pressure transmitting valve assemblies convert the differential pressure signal collected into a standard electrical signal.

Secondary display and totalization instrument: The flow totalizer receives signals from the transmitter, calculates flow and displays instantaneous and cumulative flow rates. Some models are equipped with temperature and pressure compensation modules.

smart orifice plate air,liquid flow meter
Orifice Flow Meter for Liquid, Gas, Steam DP Flow Measurement
Insertion Installation Annubar Flow Meter for All Industries
venturi flowmeter 3
Venturi Flow Meter – Classic Venturi Tube Design
V-Cone Flow Sensor with Condenser
V Cone Flow Meter-New Type DP Flow Meter
Sanitary Target Flow Meter
Intelligent Target Flow Meter
Metal Rotameter
Metal Rotameter/Variable Area Flow Meters

Installation Precautions for Orifice Plate Flow Meters

Before installation, verify the parameters on the nameplate and thoroughly purge the pipeline; ensure the orifice plate is correctly oriented with the sharp edge facing upstream, and that it is concentric with the pipeline; gaskets must not protrude into the flow path and cause turbulence.

Based on the orifice ratio and upstream flow-restricting elements, choose upstream and downstream straight pipe sections and remove protruding obstructions like weld spatter and temperature-measuring elements within straight pipe sections.

For horizontal pipelines, select the pressure tapping orientation based on the medium: 45° from the bottom for liquids, 45° from the top for gases, and from the side for steam, whilst ensuring the liquid level in the condensate trap is level.

Pressure taking pipes shall be laid suitably with a gradient of ≥1:12. Liquid pipes shall slope downwards and gas pipes upwards. The length should be as consistent as possible with the ambient temperature so that gas or liquid do not accumulate.

Prefer locations free from strong vibrations and strong magnetic fields. In vertical pipes the fluid should flow upwards as far as possible. The pressure-taking holes shall have no burrs, and the pressure-taking method shall comply with the design.

After installation, pressure testing and leak detection should be performed; the three-valve manifold and differential pressure transmitter should be connected according to the specifications; during commissioning, unidirectional pressure should not be applied to the transmitter, otherwise it may cause damage.

Orifice Plate Flow Meter Installation

Pre-installation Preparation

1. Verify the model numbers, nominal pressures and materials of the orifice plate, mating flanges, sealing gaskets, pressure-taking fittings, valves and other components to ensure they are compatible with the process piping, the medium being measured, and the temperature and pressure conditions; Carefully inspect the orifice plate body; the sharp edges of the orifice must be free from defects such as burrs, dents, scratches or deformation. Do not use the orifice plate if any damage is found.

2. Clean inside the upstream and downstream pipework thoroughly to remove the welding slag, scale, metal debris and other foreign matter. The high-velocity media may scratch the sharp edges of the orifice plate when purging or commissioning, which will cause measurement inaccuracies.

3. Check the lengths of the straight pipe sections upstream and downstream, and the sections after flow restricting components such as elbows, tees, control valves and reducers must meet the standard requirements for straight pipe sections, check the flow direction markings on the pipework to ensure they are consistent with the flow direction markings on the orifice plate body.

4. Prepare the installation tools: torque wrench, spirit level, grease, etc. Check that the differential pressure transmitter, pressure-taking lines, condenser (for steam applications) and isolation tank (for corrosive media) are in good condition, with no damage or blockages.

Installation Procedure

Horizontal Installation

1. Orifice plate throttling devices should preferably be installed on horizontal straight pipe sections. The position of the pressure taps should be selected according to the type of medium: for liquid media, the pressure taps should be located on either side of the horizontal centreline of the pipe; for gaseous media, the pressure taps should be located on the upper half of the pipe; for steam media, the pressure taps should be located at the horizontal centreline of the pipe to prevent the accumulation of liquid or gas.

2. The opening of the orifice plate shall be concentric with the pipe, and the end face of the orifice plate shall be perpendicular to the axis of the pipe; skew or eccentricity shall not occur.

3. Straight pipe of sufficient length must be installed upstream and downstream of the orifice plate to meet regulatory requirements and to reduce flow disturbances caused by flow disrupting components such as bends, valves and reducers.

4. The inner diameter of the gasket should be not less than the diameter of the pipe, otherwise the gasket will protrude into the pipe which will cause additional throttling and affect the accuracy of measurement.

5. Differential pressure conduits must maintain a reasonable gradient: liquid conduits should slope downwards towards the transmitter, whilst gas conduits should slope upwards towards the transmitter to facilitate the drainage of gas or accumulated liquid.

Vertical Installation

1. When installing in vertical pipework, give priority to fluid flow from bottom to top to prevent solid impurities in the medium from settling and accumulating upstream of the orifice plate; for top-to-bottom flow conditions, assess whether the medium is prone to sedimentation.

2. Ensure that the orifice plate is concentric and vertical; the required lengths of the upstream and downstream straight pipe sections are the same as for horizontal installation.

3. Position the pressure tapping ports away from directly above or below the pipe to prevent gas from accumulating at the tapping ports or solid impurities from blocking the pressure tapping holes.

4. Lay out the pressure-taking lines appropriately; fit pressure-taking lines for liquid media with air vents, and those for gas media with drain valves.

5. Allow sufficient maintenance space during installation to facilitate the subsequent removal of the orifice plate for inspection, cleaning and replacement.

Post-installation Commissioning and Inspection

1. Upon completion of installation, carry out a hydrostatic or air-tightness test on the flange sealing surfaces, pressure-taking connections and valve joints. Increase the pressure gradually and carefully check for any leaks; if a leak is detected, the pressure must be relieved before retightening or replacing the seals. Under no circumstances should work be carried out whilst the system is under pressure.

2. Bleed air and drain liquid from pressure tapping lines. For liquid media, vent air bubbles from the lines. For gaseous media, completely drain any accumulated liquid from the lines. For steam measurement circuits, pre-fill with condensate to ensure consistent condensate levels on both sides.

3. Check in detail the open/closed position of all valves, check the position of pressure-taking valves, balancing valves and drain valves. Carry out zero-point calibration on the differential pressure transmitter, set the measurement range and compensation parameters of the instrument according to the specifications of the orifice plate.

4. Keep detailed installation records including the locati0n of the installation, the lengths of the straight pipe sections upstream and downstream, the tightening torque of the bolts, the test pressure and results, and file all records in an archive.

5. During commissioning, slowly open the process valves upstream and downstream so as not to cause sudden pressure surges which may damage the orifice plate. After the system stabilizes, monitor the differential pressure and flow rate readings to confirm that the readings are steady with no significant fluctuations and no abnormal alarms are triggered.

Orifice Flow Meter Installation 2

Calibration of Orifice Flow Meters

Zero point calibration:

Open the balancing valve of the three-valve manifold and close the pressure taking valves of the high and low pressure sides to connect the high and low pressure chambers of the differential pressure transmitter, so as to set differential pressure to zero.

In this state, zero-point calibration is done to eliminate the zero-point drift caused by the installation and pressure-taking piping, so that the flow reading is 0 when the differential pressure is 0.

Parameter Verification:

Referring to the orifice plate calculation sheet, verify each configuration parameter within the instrument item by item, including the orifice diameter, pipe internal diameter, design range, medium density, and parameters relating to temperature and pressure compensation, to ensure that the parameters are entered accurately and are consistent with the design documentation.

Range verification:

Where on-site verification conditions are available, use a standard signal source to input simulated differential pressure signals (such as full-scale and half-scale) to the differential pressure transmitter. Observe the corresponding flow output and display values of the instrument to verify that the conversion relationship is accurate.

Commissioning Comparison:

After confirming the correctness of zero point and parameters, slowly close the balancing valve, and sequentially and smoothly open the pressure-taking valves on the high-pressure side and low-pressure side.

Observe the transmitter’s differential pressure and flow rate displays and, given the on-site process conditions, make a determination as to whether the values are stable, without frequent fluctuations or abnormal deviations.

Advantages of Orifice Plate Flow Meters

1. Simple structure; robust and reliable; no moving parts; good long-term operational stability; long service life.

2. Low manufacturing costs; mature supporting components; full range of specifications; suitable for various pipe diameters; easy to purchase and maintain.

3. High degree of standardisation; established calculation standards; when installation conditions are met, dry calibration can be performed without the need for actual flow calibration.

4. Suitable for a wide range of media; capable of measuring various single-phase fluids such as gases, liquids and steam; resistant to high temperatures and high pressures.

5. Flexible installation options, including flanged and angle-mounted pressure tapping, facilitating on-site retrofitting.

6. The output signal is a differential pressure signal, which can be used directly with standard differential pressure transmitters, and has high compatibility with related instruments.

Orifice Flow Meter Installation 1

The classic answer for differential pressure flow measurement is the orifice plate flowmeter, and correct installation is vital for stable and accurate measurements. Sion-Inst has a full range of differential pressure flowmeters, rotor type, V-cone type, Venturi type, Orifice type, and can be selected according to the characteristics of the medium, operating conditions and accuracy requirements.

We offer a full service including instrument supply, technical support and on-site guidance to ensure stable and reliable operation of flow measurement and control systems in different industries.

Welcome To Share This Page:
Product Categories
Latest News
Get A Free Quote Now !
Contact Form Demo (#3)

Related Products

Related News

Orifice plate flow meters measure flow based on the principle of differential pressure caused by throttling, and the measurement results

Both Type J and Type T thermocouples are widely used in industrial applications. Based on different conductor pairings, they differ significantly in

We include temperature and pressure compensation in our vortex flow meters to ensure that changes in fluid temperature and pressure

In fluid metering systems, flow totalizers receive signals from flowmeters to perform flow integration and total volume calculation. They are

In urban gas transmission and distribution, industrial boilers, kilns, CNG filling stations, and trade transfer scenarios, the precise measurement of

Dairy processing environments impose stringent requirements regarding hygiene and measurement stability; bubbles, fouling and CIP/SIP cycles can all interfere with

In modern industrial production, flow meters serve as vital instrumentation for measuring and monitoring fluid flow rates. To address the

In the monitoring of flow in gas and air pipelines, thermal dispersion and paddle type flow switches are the two

Hydrogen is a medium characterized by low density and high permeability, making flow measurement a technically challenging task. Hydrogen flow